SANS 10400‑XA — Floors

Implements 5.4.1 (underfloor heating) and 5.4.2 (suspended floors by energy zone). Enter the insulation R‑values below to check compliance.

1) Project context

Auto‑syncs with Basics.
Per 5.4.2, insulation must retain properties under moist conditions.

2) Insulation R‑values

Assembly Insulation R (m²·K/W) Requirement Status
Heated slab (underfloor heating present)
or
Helper: R = t/1000 ÷ k
Suspended floor (envelope)
or
Helper: R = t/1000 ÷ k
5.4.1 — Heated floors: insulation R ≥ 1.0 m²·K/W to prevent heat loss to ground. 5.4.2 — Suspended floors in the building envelope: Zones 1,2,6,7 → R ≥ 1.5; Zones 3,4,5,5H → R ≥ 1.0. Moisture‑resistance of the insulation is required.